Lessons and the learning game

AC power

Why volts times amps is not watts on AC, on a 12 V bench: phasors, reactance, impedance, power factor and correction, ending in a motor's power bill.

The bench

Every lesson runs on the same idea: a scaled motor on a function generator at 60 Hz and about 12 V RMS, the size of a bench transformer's secondary. The motor is what an induction motor looks like to the line, a resistance in series with an inductance: 300 ohms and 400 ohms of reactance, the 3-4-5 triangle. Mokxi has no AC induction motor part, so the course says so and uses that model, which is how motors are drawn on paper anyway.

Meters on AC volts and AC amps read true RMS, which is exactly the length of each phasor, so every step is graded from a meter rather than from a trace. The generator has its own 50 ohms inside, as a real one does, and the lessons point out where that moves a reading.

Take the course AC power on /learn.

The 120 V motor

Two lessons add a PZEM-004T energy meter on an Uno, running the gallery's PZEM-004T energy monitor sketch. Its mains side is a set of numbers on the part's sliders (120 V, the current, the power factor and 60 Hz), so the course can talk about a real shop motor without any mains in the simulation. A real PZEM is wired to live mains and must be connected by a qualified person.

The lessons

  1. Phasors without fear: 7.2 V and 9.6 V that add up to 12 V as a right triangle.
  2. Reactance: an inductor and a capacitor, each worth 400 ohms at 60 Hz, going opposite ways with frequency.
  3. Impedance: Z = V / I, a series capacitor that raises the current, and one that cancels the inductor.
  4. Real, reactive and apparent: watts, var and VA from the meters, and a pure heater for comparison.
  5. Power factor: P / S on the energy meter and the bench, light load, and what the energy counter bills.
  6. Correction capacitors: the line current falls while the motor's does not, half a capacitor, too much, and the 0.95 target.
  7. Boss build: a motor's power bill: read a new motor, size its capacitor for 1.0 and 0.95, prove it on the bench, and write the sheet for a motor of your own.

Safety

Everything in the course is low voltage. Correction capacitors on a real building are listed, AC-rated parts with bleeder resistors, and installing them is licensed electrical work under local code. Tariff notes about demand charges and power factor penalties are informational and vary by utility.

Before and after

The course builds on AC, signals and filters (RMS and resonance) and sits beside Transformers in practice, which sizes a transformer in VA.